Installation/Operation/MaintenanceTumble Dryers25 Pound (11.3 Kilogram) Capacity30 Pound (13.6 Kilogram) Capacity35 Pound (16 Kilogram) CapacityStacke
Gas Steam Electric030 Series CHD30G2-CA030LCHD30G2-CA030NCHD30G2-CT030LCHD30G2-CT030NCHD30G2-CU030LCHD30G2-CU030NCK030NCK030RCT030RCU030RDR30G2-BA030L
S Models TMB1345R_SVG H Models TMB1346R_SVG Figure 48U Models TMB1371R_SVG Y Models TMB2370N_SVGSTARTSTOPBACK Figure 49C, D, and I Models TMB1375R_SVG
1. Press the or keypad to change cycles. The center high-lighted position is the selected cycle.To customize a cycle, refer to the Programming Ma
IMPORTANT: To stop the tumble dryer at any timeduring the cycle, OPEN DOOR. To restart the tumbledryer, CLOSE door and press START button.5. When th
DefaultPro-gramsDryTime(Min.)CoolTime(Min.)Temp.Set PointRe-vers-ing5 – ExtraDry5 2 150ºF [66ºC] NoNOTE: If an altered program is determined to be cor
and DIP switch #3 on the DMP must be in the OFF position andthe DMP must be connected to the Reversing Timer Board forproper operation. The DMP settin
Description of the OPL Control PanelTMB1956N_SVG68782134510111291. START. Starts or resumes the current program or cycle.2. STOP. Temporarily halt
Function OPL Coin7 Safety Tumble (OPL) or CoinCount/Pay (Coin)ON OFF #1 #7 DIP SWITCHOFF ON SAFETY TUMBLEOFF OFF NO SAFETY TUM-BLEON ON COIN COUNTON O
Description of The Coin Control PanelTMB1955N_SVG9876543121. Clock Symbol. This symbol of a clock indicates that thetime in the display is counting
StopWhen in the Coin mode, the tumble dryer will stop if the tumbledryer door is opened while the tumble dryer is running. If theCLEAR button, located
Troubleshooting GuideThermostat on, no spark or valve 1. Cable connects to control and electrode. Voltage present atgas valve.2. Bad control. Check re
Gas Steam ElectricT30 Series CHD30STG2-CAT30LCHD30STG2-CAT30NCHD30STG2-CTT30LCHD30STG2-CTT30NCHD30STG2-CUT30LCHD30STG2-CUT30NDR335DR335G2-BKT30NDR335G
Normal OperationOnce a flame has been established, the spark ignitor will stopsparking and the control will continually monitor all inputs. If thecont
System TestsThe following system tests are performed during normal opera-tion. System tests are performed at a minimum of every 24 hours.Low Voltage
Adjustments AdjustmentsWARNINGTo reduce the risk of electric shock, fire, explosion,serious injury or death:• Disconnect electric power to the tumble
T457I_SVG4142431. Proper Airflow2. Insufficient Airflow3. No Airflow4. Air Shutter Adjusting ScrewFigure 59 Airflow SwitchThe airflow switch i
TMB2105N_SVG11. Switch ActuatorFigure 60 Door StrikeThe door strike must be adjusted to have sufficient tension tohold loading door closed against f
Maintenance Daily1. Inspect the area surrounding tumble dryers, remove all com-bustible materials, including lint, before operating the ma-chines.2.
7. Models equipped with a fire suppression system: Performthe fire suppression system maintenance test by pressing thetest button in the control box
7. After 15 seconds of water spray, press and hold the reset but-ton until water spray is off and light is off. This should takeapproximately one se
Before You Call for ServiceWon’t Start Won’t Heat Clothes Not Dry Possible Reason – Corrective Actions• Insert correct coin(s) or valid card if applic
Removing Tumble Dryer from Service1. Turn off electrical supply external to machine.2. Turn off electrical disconnect on machine.3. Turn off gas
Gas Steam Electric035 Series AT035LAT035NCHD35G2-CA035LCHD35G2-CA035NCHD35G2-CT035LCHD35G2-CT035NCHD35G2-CU035LCHD35G2-CU035NCK035NCK035RCT035RCU035RD
Disposal of UnitThis appliance is marked according to the European directive2002/96/EC on Waste Electrical and Electronic Equipment(WEEE).This symbol
Gas Steam ElectricT45 Series DR445G2-BAT45LDR445G2-BAT45NDR445G2-BKT45NDR445G2-BKT45RDR445G2-BTT45DDR445G2-BTT45LDR445G2-BTT45NDR445G2-BTT45RDR445G2-B
Gas Steam Electric055 Series CA055LCA055NCK055NCK055RCT055LCT055NCT055RCU055LCU055NCU055RDR55SG2-BA055LDR55SG2-BA055NDR55SG2-BK055NDR55SG2-BK055RDR55S
3B – reversing DX4 vended3K – reversing DX4 prep for central pay3L – DX4 prep for central pay3O – DX4 OPL3V – DX4 vended3W – reversing DX4 prep for co
WARNINGTo reduce the risk of serious injury or death, DONOT repair or replace any part of the unit or attemptany servicing unless specifically recomme
Safety Information Explanation of Safety MessagesPrecautionary statements (“DANGER,” “WARNING,” and“CAUTION”), followed by specific instructions, are
• Always read and follow manufacturer’s instructions on pack-ages of laundry and cleaning aids. Heed all warnings or pre-cautions. To reduce the risk
Specifications and Dimensions Specifications and DimensionsRefer to machine serial plate for additional specifications.Specifications 025 Series 030 S
Specifications 025 Series 030 Series 035 Series 055 SeriesMaximumAirflow perPocket:C.F.M.[l/sec]50HertzClassic Line430 [203]Eco Line250 [118]430 [203]
Specifications 025 Series 030 Series 035 Series 055 SeriesSteam Connection 3/4 in. NPT 3/4 in. NPT 3/4 in. NPT N/ASteam Coil Rating at100 psig: Boiler
Specifications T30 Series T45 SeriesMaximum Airflowper Pocket**:C.F.M. [l/sec]50 Hertz Classic Line340 [160]Eco Line225 [106]500 [236]60 Hertz Classic
Specifications T30 Series T45 SeriesSteam Coil Rating at 100 psig**:Boiler Horsepower [Btu/hr.] (recom-mended operating pressure 80-100 psig)3.2 [111,
Models G H* I* J* K L030 Series 63.875 in.[1,622 mm]16.48 in. [419mm]15.41 in. [391mm]1.59 in. [40mm]24.64 in. [626mm]28 in. [711mm]035 Series 63.875
Models A B C D ET45 Series 29.37 in. [746mm]48.62 in. [1,235mm]30.50 in. [775mm]34.5 in. [876 mm] 81.25 in. [2,063.75mm]NOTE: To meet ADA compliance,
ModelsRear ExhaustDiameter A B055 Series 8 in. [203 mm] 4.808 in. [122 mm] 6.156 in. [156.3 mm] Exhaust Outlet Locations – T30 and T45 SeriesTMB1969N_
Gas Connection Locations – 025, 030, 035 and 055 SeriesTMB2106N_SVGACB11. 1/2 in. NPTModelsGas Connection – CE and Australian UnitsA B C25 Series 5
Gas Connection Locations – T30 and T45 Series TMB1970N_SVG CBA11. 1/2 in. NPTModelsGas ConnectionA B CT30 Series Non-CE and Non-Aus-tralian75.20
Electrical Connection Locations – 025, 030, 035 and 055 SeriesTMB2204N_SVG BCDA211. Gas and Steam2. ElectricModelsElectrical ServiceGas and Steam
Front MatterInstallation must conform with local codes or, in the absence of local codes, with:In the U.S.A., installation must conform to the latest
Electrical Connection Locations – T30 and T45 SeriesTMB1971N_SVGEDCBA211. Gas and Steam2. ElectricModelsElectric ServiceGas and Steam Models Elec
Steam Connection Locations – 025, 030 and 035 SeriesTMB2108N_SVGDCBAModelsInlet OutletA C B D025/030/035 Series 53.75 in. [1,365 mm] 6.29 in. [160 mm
Steam Connection Locations – T30 SeriesTMB1972N_SVGBADCBAModelsInlet OutletA C B DT30 Series (Upper) 73.93 in. [1,877 mm] 6.29 in. [160 mm] 62.71 in.
Installation Pre-Installation InspectionUpon delivery, visually inspect the crate, carton and parts for anyvisible shipping damage. If the crate, cart
TMB2021N_SVG43165827NOTE: Shaded areas indicate adjacent structure.1. 0.5 in. [13 mm] recommended between machines for removal or installation2. A
CAUTIONThe stacked tumble dryer has a 5th leveling leg onthe blower housing. It is very important to properlyadjust this leg. Unit is back heavy and c
TMB2248N_SVG 1231. Fire Suppression System Control Box2. Water Solenoid Valve3. Opening for Auxiliary Alarm CableFigure 5To connect the two hose
TMB1999N_SVG1675431 21. Opening for Auxiliary Alarm Cable2. Fuse3. Auxiliary Alarm Fast-On Connection4. Test Button5. Light6. Reset Button
TMB2101N_SVG534211. Plug2. Switch3. Door Hinge Lug4. Door Assembly5. Side ScrewFigure 97. Cut wire ties to remove door switch harness bund
TMB2102N_SVG43211. Switch (New location)2. Plug (New location)3. Door Assembly4. Side ScrewFigure 11NOTE: If machine is converted back to righ
WARNING• Installation of unit must be performed by a qualified installer.• Install tumble dryer according to manufacturer’s instructions and local cod
T452I_SVGFigure 13ModelsPrepurge Time(seconds)Trial for Ignition(seconds)Reset Lockout Con-dition By:Models through3/10/13CE andAustralia18 10 025, 03
Required for CE Models OnlyOnce machine is installed, please be sure to complete the follow-ing items:• Review and verify machine operation with cust
GasTypeGasFamilyGasGroupGas Desig-nationSupplyPressurein. wc[mbar,kPa]Mani-foldPres-surein. wc[mbar,kPa]Ca-pacityModelOrificeDiame-ter in.[mm]OrificeP
GasTypeGasFamilyGasGroupGas Desig-nationSupplyPressurein. wc[mbar,kPa]Mani-foldPres-surein. wc[mbar,kPa]Ca-pacityModelOrificeDiame-ter in.[mm]OrificeP
GasTypeGasFamilyGasGroupGas Desig-nationSupplyPressurein. wc[mbar,kPa]Mani-foldPres-surein. wc[mbar,kPa]Ca-pacityModelOrificeDiame-ter in.[mm]OrificeP
GasTypeGasFamily GroupGasDe-scrip-tionGasDesig-nationWi Hi Ws Hs dWobbeIndex(net)Heat-ingValue(net)WobbeIndex(gross)Heat-ingValue(gross)Densi-tyBtu/ft
NOTE: Conversion from regulated to unregulated is on-ly needed when regulated tumble dryers were ordered,but unregulated tumble dryers were needed.1.
Models Starting 1/1/14TMB2405N_SVG1924756831. Gas Valve2. Manometer3. Required Burner Manifold Pressure4. Connect Over Loosened Hex Pressure T
Exhaust Requirements Exhaust RequirementsWARNINGA drying tumble dryer produces combustible lint. Toreduce the risk of fire, the tumble dryer must be e
Verify that old ducts are thoroughly cleaned out before installingnew tumble dryer(s).WARNINGImproperly sized or assembled ductwork causes ex-cess bac
Table of ContentsIntroduction... 9Model Identification...
a rectangular duct must be increased by 20% for each additional20 feet [6.1 m] . Refer to Table 3 to determine equivalent vent-ing.Duct DiameterEquiva
One Manifold AssemblyTMB2403N_SVGLKJIHGFEDCBA121. Outlet duct diameter = largest duct diameter based on number of units2. 45° typicalFigure 20Duct
Two Manifold AssembliesTMB2018N_SVG12L LK KJ JIAAI1. Outlet duct diameter = combined largest duct diameter of both sides2. 45° typicalFigure 21Ref
Gas Requirements Gas RequirementsWARNINGTo reduce the risk of fire or explosion, DO NOT CON-NECT THE GAS LINE TO THE TUMBLE DRYER IFTHE GAS SERVICE IS
Non-CEand Non-AustralianModelsAustralianand Kore-an ModelsCE Mod-elsRecommend-ed11 in. w.c. 2.74 kPa 27.4 mbarMinimum 10 in. w.c. 2.49 kPa 24.9 mbarFo
Gas Supply Pipe Sizing and LoopingTMB2126N_SVG1 2 3 4 5 6 7 8 9M687453219 1011121. Gas furnace [120,000 Btu/hr. [127 Mj/hr., 35.2 kW]]2. Gas wate
Gas Pipe Size Required for 1000 Btu Natural Gas — 0.64 Specific Gravity at 7 ± 1.5 inches [17.4 ± 4 mbar, 1.74 ± 0.37kPa] Water Column PressureGasAppl
Gas Pipe Size Required for 1000 Btu Natural Gas — 0.64 Specific Gravity at 7 ± 1.5 inches [17.4 ± 4 mbar, 1.74 ± 0.37kPa] Water Column PressureGasAppl
Classic Line ModelsModel GasAltitude Burner Orifice New Ratefeet [meters] No.inches[ mm]Quanti-ty Part No.Btu/hr.*[Mj/hr.]025 Series NaturalGas2,001-4
Model GasAltitude Burner Orifice New Ratefeet [meters] No.inches[ mm]Quanti-ty Part No.Btu/hr.*[Mj/hr.]T30 Series NaturalGas2,001-4,000[ 610-1,220]22
Exhaust Requirements...48Exhaust Requirements...
Model GasAltitude Burner Orifice New Ratefeet [meters] No.inches[ mm]Quanti-ty Part No.Btu/hr.*[Mj/hr.]T45SeriesNaturalGas2,001-4,000[ 610-1,220]15 0.
Eco Line ModelsModel GasAltitude Burner Orifice New Ratefeet [meters] No.inches[ mm]Quanti-ty Part No.Btu/hr.*[Mj/hr.]025 Series NaturalGas 50Hz2,001-
Model GasAltitude Burner Orifice New Ratefeet [meters] No.inches[ mm]Quanti-ty Part No.Btu/hr.*[Mj/hr.]T30 Series NaturalGas 50Hz2,001-4,000[ 610-1,22
Model GasAltitude Burner Orifice New Ratefeet [meters] No.inches[ mm]Quanti-ty Part No.Btu/hr.*[Mj/hr.]T45SeriesNaturalGas 50Hz2,001-4,000[ 610-1,220]
Model GasAltitude Burner Orifice New Ratefeet [meters] No.inches[ mm]Quanti-ty Part No.Btu/hr.*[Mj/hr.]*Btu/hr. derate of 4% per 1,000 feet [305 meter
Electrical Requirements Electrical RequirementsWARNINGTo reduce the risk of electric shock, fire, explosion,serious injury or death:• Disconnect elect
Start Pulse RequirementsAll control types will consider a pulse valid if it is between 200and 1000 milliseconds in length, with a minimum of 200 milli
WARNINGTo reduce the risk of electrical shock, de-energizethe electrical circuit being connected to the tumbledryer before making any electrical conne
Models Through 7/9/12 Heat Source Ground and Terminal Block LocationsCE025030035055Gas or SteamTMB2129N_SVG2 311. Models Through 7/31/112. Ground
Models Starting 7/10/12 Ground and Terminal Block LocationsCE025030035055Control TrayTMB2379N_SVG211. Power Distribution Block2. GroundTable 9Mode
Error Codes...92Operating Instructions...
Model Heat SourceGround and Terminal Block Loca-tionsCET30/T45T30: Gas or Steam T45: GasTMB2114N_SVG2311. Terminal Block2. Power Disconnect (Model
ModelsIf your SerialPlate voltageis:Your tumbledryer can beconverted tothe followingvoltages:025, 030, 035,055, T30200 Volt/50Hertz/1 Phase100 Volt/50
Conversion InstructionsIf serial plate voltage is: Tumble Dryer can be converted to the following voltages:120 Volt/60 Hertz/1 Phase2W&G(All mode
If serial plate voltage is: Tumble Dryer can be converted to the following voltages:200-220 Volt/60 Hertz/1 Phase200 Volt/50 Hertz/1 Phase2W&G(All
TMB2096N_SVG1321. Ferrite Ring2. Electrical Connections V.A.C.3. Ground WireFigure 26 Electrical SpecificationsNOTE: Wire sizes were obtained fr
100V/50Hz/1ph L1, Neutral, andground12.1 N/A 20A – 1 pole 12 [4]200V/50Hz/1ph L1, Neutral, andground7.5 N/A 10A – 1 pole 14 [2.5]230-240V/50Hz/1phL1,
100V/60Hz/1ph L1, Neutral, andground9.8 N/A 15A – 1 pole 14 [2.5]100V/50Hz/1ph L1, Neutral, andground10 N/A 15A – 1 pole 14 [2.5]200V/50Hz/1ph L1, Neu
230-240V/50Hz/1ph L1, Neutral, andground9.0 15A – 1 pole 14 [2.5]200-208V/60Hz/3ph L1, L2, L3, and ground 6.4 10A* – 3 pole 14 [2.5]240V/60Hz/3ph L1,
400V/50Hz/3ph L1, L2, L3, andground16 N/A 20A* – 3 pole 12 [4]* 3 Phase machines should not have fuses, breakers only.N/A = Not ApplicableTable 159 kW
200V/50Hz/1ph L1, Neutral, andground63 N/A 80A – 1 pole 4 [25]200V/60Hz/1ph L1, L2 and ground 64 N/A 80A – 2 pole 4 [25]230-240V/50Hz/1phL1, Neutral,
Removing Tumble Dryer from Service... 119Disposal of Unit...
230-240V/50Hz/1ph L1, Neutral, andground95 N/A 125A – 2 pole 1 [35]200-208V/60Hz/3ph** L1, L2, L3, andground62 62 80A* – 3 pole 4 [25]200V/50Hz/3ph**
440V/60Hz/3ph** L1, L2, L3, andground17.2 17.2 25A* – 3 pole 10 [6]460-480V/60Hz/3ph** L1, L2, L3, andground15.7 15.7 20A* – 3 pole 12 [4]* 3 Phase ma
400-415V/50Hz/3ph* L1, L2, L3, and ground 35** 50A – 3 pole 10 [6]440V/60Hz/3ph* L1, L2, L3, and ground 17** 25A – 3 pole 10 [6]460-480V/60Hz/3ph* L1,
460-480V/60Hz/3phL1, L2, L3, andground31 31 40A* – 3 pole 8 [10]* 3 Phase machines should not have fuses, breakers only.N/A = Not ApplicableTable 2212
200V/60Hz/1ph L1, Neutral, andground122 N/A 175A – 1 pole 2/0 [70]200V/50Hz/1ph L1, Neutral, andground131 N/A 175A – 1 pole 2/0 [70]230-240V/50Hz/1phL
Steam Requirements Steam RequirementsNOTE: Machines require a constant 80 to 100 psig [5.3to 6.9 bar] steam service for optimum operation. Themaximum
T473I_SVG9751041054211186312NOTE: Refer to Table 26 for sizing of steam lines. Piping must also be sized accordingly for length of runs andnumber of e
ModelSteam PressurePSI [ bar]Minimum Supply PipeDiameterSteam Trap Size*Pounds Condensate/Hour[Kilograms Condensate/Hour]035 Series 80-100 [5.3-6.9] 3
Single Drop TimerNOTE: The following information is for models with anSD control suffix only. Power-Up ModeWhen power is applied to the tumble dryer,
To reset the time, unplug the tumble dryer and set dipswitch 8 toON position. Restore power to the tumble dryer for 10 secondsand once again unplug tu
Introduction Model IdentificationInformation in this manual is applicable to these models:Gas Steam Electric025 Series CHD25G2-CA025LCHD25G2-CA025NCHD
Heat TimePer CoinPulse (in mi-nutes)Heat Switch Number1 2 3 4 5 623 OFF ON ON OFF ON OFF24 ON ON ON OFF ON OFF25 OFF OFF OFF ON ON OFF26 ON OFF OFF ON
Heat TimePer CoinPulse (in mi-nutes)Heat Switch Number1 2 3 4 5 649 OFF OFF OFF OFF ON ON50 ON OFF OFF OFF ON ON51 OFF ON OFF OFF ON ON52 ON ON OFF OF
Cool Down Per Cycle (in minutes)Cool Down Switch Number4 ON ONModels Starting Serial No. 0909xxxxxCool DownPer Cycle (inminutes)Cool DownSwitch Num-be
Operating Instructions Operating InstructionsWARNINGTo reduce the risk of fire:• DO NOT DRY articles containing foam rubber orsimilarly textured rubbe
IMPORTANT: Clean lint screen and lint compart-ment daily. Failure to clean the lint screen daily willresult in higher than normal temperatures that ma
TMB2149N_SVGFigure 324. Select reversing or nonreversing cylinder rotation setting, ifapplicable.TMB2145N_SVGFigure 335. Press and release START b
Error CodesDisplay Definition Corrective ActionAF (Flashing) Bouncing Airflow Switch • Check airflow switch to ensure that it is properly alignedand s
NOTE: The window display will flash. Press STOP/RESET twice (within three seconds) to end the cycleand reset the control to idle status. To restart th
3. Press START pad to start tumble dryer.TMB2331N_SVGFigure 45IMPORTANT: To stop the tumble dryer at anytime during the cycle, OPEN DOOR. To restart
4. When the cycle is complete, open door and remove the laun-dry.WARNINGTo prevent the risk of fire, remove laundry imme-diately in case of power fa
Comentarios a estos manuales